Insulating Refrigerant Pipes
Overlap insulation to avoid gaps.
Avoid compressing the insulation as much as possible.
Be sure there are no cracks or deformities in the insulation at bends in pipes or where
hangers are attached to pipes.
If necessary, double the insulation to prevent condensation from forming in warm or humid
areas.
3. Clamp insulation tightly to pipes.
4. Cut off excess insulation.
Clamp
Insulation
Gas side pipe
Liquid side pipe